ApprovedFiled May 22, 2025 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- May 22, 2025
- Assembly type
- PVB
- Serial number
- A363602
- Size
- 3/4
- Test gauge serial
- G-7460
- Gauge calibration date
- Mar 14, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-59-01086
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.