Back to the backflow review queue

Backflow assembly test: 6284 Hickory Ln

Approved

Filed Oct 8, 2024 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Oct 8, 2024
Assembly type
DC
Serial number
W966316
Size
1
Test gauge serial
G-5100
Gauge calibration date
Jun 26, 2024
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-57-01026
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6284 Hickory Ln
Owner: Cameron Marsh
Parcel 051-57-01026