Backflow assembly test: 6284 Hickory Ln

Approved

Filed Sep 18, 2025 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Sep 18, 2025
Assembly type
DC
Serial number
W966316
Size
1
Test gauge serial
G-7280
Gauge calibration date
Aug 29, 2024
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
3.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-57-01026
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6284 Hickory Ln
Owner: Cameron Marsh
Parcel 051-57-01026