Back to the backflow review queue
Backflow assembly test: 3057 Quarry Rd
ApprovedFiled Sep 21, 2025 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 21, 2025
- Assembly type
- DC
- Serial number
- B443082
- Size
- 3/4
- Test gauge serial
- G-1300
- Gauge calibration date
- Nov 28, 2024
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-11-01155
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3057 Quarry Rd
Owner: Emerson Calloway
Parcel 051-11-01155