Back to the backflow review queue

Backflow assembly test: 5240 Quarry Dr

Approved

Filed Mar 31, 2026 by Shawn Nguyen, Valley Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Mar 31, 2026
Assembly type
RP
Serial number
Z707553
Size
1
Test gauge serial
G-9950
Gauge calibration date
Oct 15, 2025
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-76-01321
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5240 Quarry Dr
Owner: Reese Ellery
Parcel 051-76-01321