Backflow assembly test: 6122 Old Church Ct
ApprovedFiled Jun 28, 2025 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 28, 2025
- Assembly type
- RP
- Serial number
- B302196
- Size
- 3/4
- Test gauge serial
- G-8948
- Gauge calibration date
- May 8, 2025
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-66-01250
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.