Back to the backflow review queue
Backflow assembly test: Golden Taqueria
ApprovedFiled Jul 8, 2025 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 8, 2025
- Assembly type
- RP
- Serial number
- B741051
- Size
- 2
- Test gauge serial
- G-9772
- Gauge calibration date
- May 10, 2025
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-95-01115
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8225 Sycamore Trl
Owner: Ramirez Holdings LLC
Parcel 051-95-01115