Backflow assembly test: Maple Leaf Apartments

Sent back

Filed Nov 25, 2026 by Avery Ramirez, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Nov 25, 2026
Assembly type
RP
Serial number
Z473358
Size
1
Test gauge serial
G-8047
Gauge calibration date
Jul 28, 2026
Check valve 1
3.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Ramirez, current on the service date
  • All required fields present
  • Address matches parcel 051-97-01153
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Sent back Please add the test gauge calibration certificate.

Property

8458 Mill Creek Trl
Owner: Fairley Holdings LLC
Parcel 051-97-01153