Backflow assembly test: 6238 Mill Creek Way

Approved

Filed Jun 7, 2023 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Jun 7, 2023
Assembly type
PVB
Serial number
W153991
Size
3/4
Test gauge serial
G-6680
Gauge calibration date
Nov 26, 2022
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-77-01128
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6238 Mill Creek Way
Owner: Taylor Nguyen
Parcel 051-77-01128