Backflow assembly test: Blue Heron Medical Offices
ApprovedFiled Oct 26, 2023 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 26, 2023
- Assembly type
- RP
- Serial number
- W661248
- Size
- 1 1/2
- Test gauge serial
- G-2952
- Gauge calibration date
- Sep 23, 2023
- Check valve 1
- 4.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-54-01357
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.