Backflow assembly test: 722 Ridgeview Rd

Approved

Filed Jun 14, 2025 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Jun 14, 2025
Assembly type
DC
Serial number
W486428
Size
3/4
Test gauge serial
G-1313
Gauge calibration date
Dec 15, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-43-01179
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

722 Ridgeview Rd
Owner: Morgan Nguyen
Parcel 051-43-01179