Back to the backflow review queue

Backflow assembly test: 6390 Cedar Hollow Ln

Approved

Filed Apr 19, 2024 by Parker Nguyen, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Apr 19, 2024
Assembly type
RP
Serial number
K800466
Size
3/4
Test gauge serial
G-4219
Gauge calibration date
Nov 6, 2023
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-36-01055
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6390 Cedar Hollow Ln
Owner: Alex Ramirez
Parcel 051-36-01055