Back to the backflow review queue

Backflow assembly test: 8867 Old Church Trl

Approved

Filed May 7, 2026 by Shawn Nguyen, Valley Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 7, 2026
Assembly type
DC
Serial number
B289398
Size
3/4
Test gauge serial
G-9077
Gauge calibration date
Mar 26, 2026
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-35-01289
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8867 Old Church Trl
Owner: Quinn Benton
Parcel 051-35-01289