Back to the backflow review queue

Backflow assembly test: 3226 Hickory Ln

Approved

Filed Jul 27, 2025 by Cameron Kessler, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 27, 2025
Assembly type
RP
Serial number
W771314
Size
1
Test gauge serial
G-4093
Gauge calibration date
Jun 21, 2025
Check valve 1
0 psid
Check valve 1 closed tight
No
Check valve 2
3.6 psid
Relief valve opened at
4.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-29-01124
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3226 Hickory Ln
Owner: Morgan Wexler
Parcel 053-29-01124