Backflow assembly test: 720 Mill Creek Ln
ApprovedFiled May 12, 2024 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 12, 2024
- Assembly type
- PVB
- Serial number
- A491413
- Size
- 1
- Test gauge serial
- G-8003
- Gauge calibration date
- Sep 9, 2023
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 053-14-01197
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
720 Mill Creek Ln
Owner: Sam Vance
Parcel 053-14-01197