Back to the backflow review queue

Backflow assembly test: Riverside Bakery

Approved

Filed Jan 12, 2026 by Parker Fairley, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 12, 2026
Assembly type
RP
Serial number
K454586
Size
2
Test gauge serial
G-8221
Gauge calibration date
Nov 23, 2025
Check valve 1
6.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 053-50-01348
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8607 Orchard Rd
Owner: Ramirez Holdings LLC
Parcel 053-50-01348