Back to the backflow review queue

Backflow assembly test: 6959 Fox Run Ln

Approved

Filed Nov 15, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 15, 2026
Assembly type
DC
Serial number
B807959
Size
3/4
Test gauge serial
G-1614
Gauge calibration date
Jul 10, 2026
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-11-01099
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6959 Fox Run Ln
Owner: Drew Danner
Parcel 053-11-01099