Backflow assembly test: Two Rivers Car Wash

Approved

Filed Feb 2, 2025 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 2, 2025
Assembly type
RP
Serial number
K116639
Size
1 1/2
Test gauge serial
G-9265
Gauge calibration date
Oct 9, 2023
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Hollins, current on the service date
  • All required fields present
  • Address matches parcel 053-36-01331
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8640 Cedar Hollow Trl
Owner: Wexler Holdings LLC
Parcel 053-36-01331