Back to the backflow review queue

Backflow assembly test: Two Rivers Car Wash

Approved

Filed Jan 18, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 18, 2026
Assembly type
RP
Serial number
K116639
Size
1 1/2
Test gauge serial
G-2044
Gauge calibration date
Apr 5, 2025
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-36-01331
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8640 Cedar Hollow Trl
Owner: Wexler Holdings LLC
Parcel 053-36-01331