Back to the backflow review queue

Backflow assembly test: 1460 Hickory Ct

Approved

Filed Dec 7, 2024 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 7, 2024
Assembly type
RP
Serial number
W333234
Size
3/4
Test gauge serial
G-4956
Gauge calibration date
Jun 23, 2024
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-20-01109
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.