Back to the backflow review queue

Backflow assembly test: 7901 Quarry Ct

Approved

Filed Jan 21, 2026 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 21, 2026
Assembly type
RP
Serial number
Z287112
Size
1
Test gauge serial
G-7456
Gauge calibration date
Nov 9, 2025
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 053-60-01316
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7901 Quarry Ct
Owner: Avery Harlow
Parcel 053-60-01316