ApprovedFiled Apr 12, 2026 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 12, 2026
- Assembly type
- RP
- Serial number
- W505059
- Size
- 1 1/2
- Test gauge serial
- G-2894
- Gauge calibration date
- Sep 16, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 053-94-01003
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.