Backflow assembly test: 1308 Mill Creek Way
ApprovedFiled May 2, 2026 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- May 2, 2026
- Assembly type
- RP
- Serial number
- Z491249
- Size
- 3/4
- Test gauge serial
- G-3976
- Gauge calibration date
- Feb 28, 2026
- Check valve 1
- 4.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Hollins, current on the service date
- All required fields present
- Address matches parcel 053-55-01105
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
1308 Mill Creek Way
Owner: Reese Nguyen
Parcel 053-55-01105