Backflow assembly test: 1308 Mill Creek Way

Approved

Filed May 2, 2026 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 2, 2026
Assembly type
RP
Serial number
Z491249
Size
3/4
Test gauge serial
G-3976
Gauge calibration date
Feb 28, 2026
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Hollins, current on the service date
  • All required fields present
  • Address matches parcel 053-55-01105
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.