Back to the backflow review queue

Backflow assembly test: Corner Brewing Co

Approved

Filed Jun 20, 2025 by Parker Fairley, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 20, 2025
Assembly type
RP
Serial number
K258754
Size
4
Test gauge serial
G-5096
Gauge calibration date
Jan 14, 2025
Check valve 1
3.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 053-70-01248
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

773 Laurel Rd
Owner: Wexler Holdings LLC
Parcel 053-70-01248