Backflow assembly test: 8676 Pine Knoll Trl

Approved

Filed Oct 7, 2025 by Cameron Kessler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 7, 2025
Assembly type
RP
Serial number
B431298
Size
1
Test gauge serial
G-8950
Gauge calibration date
Feb 20, 2025
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Kessler, current on the service date
  • All required fields present
  • Address matches parcel 053-74-01011
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8676 Pine Knoll Trl
Owner: Logan Okafor
Parcel 053-74-01011