Backflow assembly test: Hilltop Grill

Approved

Filed Aug 4, 2025 by Rowan Benton, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 4, 2025
Assembly type
RP
Serial number
W437197
Size
1 1/2
Test gauge serial
G-8859
Gauge calibration date
Apr 24, 2025
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-70-01070
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3679 Sycamore Rd
Owner: Kessler Holdings LLC
Parcel 053-70-01070