Backflow assembly test: 4110 Hickory Ct

Approved

Filed Jan 11, 2026 by Parker Pruitt, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 11, 2026
Assembly type
RP
Serial number
K453686
Size
1
Test gauge serial
G-5928
Gauge calibration date
Nov 10, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 053-91-01219
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.