Backflow assembly test: 3126 Hickory Ln
ApprovedFiled Jun 10, 2023 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 10, 2023
- Assembly type
- RP
- Serial number
- Z548906
- Size
- 1
- Test gauge serial
- G-2457
- Gauge calibration date
- Dec 16, 2022
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Pruitt, current on the service date
- All required fields present
- Address matches parcel 053-75-01006
- Readings in range, no flags
- Result: passing. Next due date resets when approved.