Backflow assembly test: 6547 Sycamore Way

Filed Nov 23, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 23, 2026
Assembly type
DC
Serial number
B264511
Size
3/4
Test gauge serial
G-7464
Gauge calibration date
Aug 19, 2026
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-15-01066
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

6547 Sycamore Way
Owner: Taylor Hollins
Parcel 053-15-01066