Back to the backflow review queue
Backflow assembly test: 6547 Sycamore Way
Needs reviewFiled Nov 23, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 23, 2026
- Assembly type
- DC
- Serial number
- B264511
- Size
- 3/4
- Test gauge serial
- G-7464
- Gauge calibration date
- Aug 19, 2026
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Benton, current on the service date
- All required fields present
- Address matches parcel 053-15-01066
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
6547 Sycamore Way
Owner: Taylor Hollins
Parcel 053-15-01066