Backflow assembly test: 8179 Laurel Rd
ApprovedFiled Jul 6, 2025 by Parker Pruitt, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 6, 2025
- Assembly type
- PVB
- Serial number
- B903857
- Size
- 3/4
- Test gauge serial
- G-9493
- Gauge calibration date
- Apr 16, 2025
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Pruitt, current on the service date
- All required fields present
- Address matches parcel 053-87-01056
- Readings in range, no flags
- Result: passing. Next due date resets when approved.