Back to the backflow review queue

Backflow assembly test: 2980 Cedar Hollow Way

Approved

Filed Oct 11, 2024 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 11, 2024
Assembly type
RP
Serial number
K190720
Size
1
Test gauge serial
G-1468
Gauge calibration date
May 28, 2024
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-98-01195
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2980 Cedar Hollow Way
Owner: Avery Harlow
Parcel 053-98-01195