Back to the backflow review queue
Backflow assembly test: 3403 Old Church Way
ApprovedFiled Aug 30, 2024 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 30, 2024
- Assembly type
- RP
- Serial number
- K623710
- Size
- 3/4
- Test gauge serial
- G-3961
- Gauge calibration date
- Feb 15, 2024
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Benton, current on the service date
- All required fields present
- Address matches parcel 053-68-01030
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3403 Old Church Way
Owner: Cameron Kessler
Parcel 053-68-01030