Back to the backflow review queue

Backflow assembly test: 4100 Quarry Way

Approved

Filed Sep 9, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 9, 2026
Assembly type
RP
Serial number
Z282234
Size
3/4
Test gauge serial
G-7693
Gauge calibration date
Jul 3, 2026
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
1.8 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-32-01353
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4100 Quarry Way
Owner: Emerson Ramirez
Parcel 053-32-01353