Backflow assembly test: 8293 Ridgeview Way

Approved

Filed Jan 24, 2024 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 24, 2024
Assembly type
RP
Serial number
K507876
Size
3/4
Test gauge serial
G-4034
Gauge calibration date
Sep 30, 2023
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Hollins, current on the service date
  • All required fields present
  • Address matches parcel 053-68-01015
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8293 Ridgeview Way
Owner: Logan Danner
Parcel 053-68-01015