Back to the backflow review queue

Backflow assembly test: 8293 Ridgeview Way

Approved

Filed Feb 10, 2026 by Rowan Benton, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Feb 10, 2026
Assembly type
RP
Serial number
K507876
Size
3/4
Test gauge serial
G-1075
Gauge calibration date
Sep 25, 2025
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Benton, current on the service date
  • All required fields present
  • Address matches parcel 053-68-01015
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8293 Ridgeview Way
Owner: Logan Danner
Parcel 053-68-01015