Back to the backflow review queue
Backflow assembly test: 670 Quarry Rd
ApprovedFiled Jan 12, 2026 by Parker Pruitt, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jan 12, 2026
- Assembly type
- RP
- Serial number
- W156913
- Size
- 1
- Test gauge serial
- G-9839
- Gauge calibration date
- Dec 9, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Pruitt, current on the service date
- All required fields present
- Address matches parcel 053-71-01222
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
670 Quarry Rd
Owner: Cameron Marsh
Parcel 053-71-01222