Backflow assembly test: 4384 Spring Branch Trl

Approved

Filed Oct 20, 2026 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 20, 2026
Assembly type
RP
Serial number
A103391
Size
3/4
Test gauge serial
G-6219
Gauge calibration date
Jan 20, 2026
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Hollins, current on the service date
  • All required fields present
  • Address matches parcel 053-83-01062
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4384 Spring Branch Trl
Owner: Rowan Hollins
Parcel 053-83-01062