Backflow assembly test: 1953 Sycamore Ct
ApprovedFiled Apr 14, 2025 by Parker Pruitt, Patriot Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 14, 2025
- Assembly type
- PVB
- Serial number
- B877779
- Size
- 1
- Test gauge serial
- G-6749
- Gauge calibration date
- Mar 3, 2025
- Check valve 1
- 6.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Pruitt, current on the service date
- All required fields present
- Address matches parcel 053-60-01202
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.