Back to the backflow review queue

Backflow assembly test: 5260 Old Church Trl

Approved

Filed May 8, 2024 by Emerson Hollins, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 8, 2024
Assembly type
RP
Serial number
A333000
Size
1
Test gauge serial
G-2218
Gauge calibration date
Apr 4, 2024
Check valve 1
6.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Hollins, current on the service date
  • All required fields present
  • Address matches parcel 053-92-01093
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5260 Old Church Trl
Owner: Logan Nguyen
Parcel 053-92-01093