Back to the backflow review queue

Backflow assembly test: Crossroads Grill

Approved

Filed Nov 1, 2025 by Cameron Ellery, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Nov 1, 2025
Assembly type
RP
Serial number
Z998279
Size
1 1/2
Test gauge serial
G-6873
Gauge calibration date
Mar 23, 2025
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Ellery, current on the service date
  • All required fields present
  • Address matches parcel 055-64-01131
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8830 Sycamore Ln
Owner: Danner Holdings LLC
Parcel 055-64-01131