Back to the backflow review queue

Backflow assembly test: 1194 Ridgeview Trl

Approved

Filed Sep 20, 2024 by Emerson Calloway, Ridge Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 20, 2024
Assembly type
RP
Serial number
W801296
Size
1
Test gauge serial
G-4827
Gauge calibration date
Mar 16, 2024
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-32-01147
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1194 Ridgeview Trl
Owner: Morgan Nguyen
Parcel 055-32-01147