ApprovedFiled Oct 15, 2025 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 15, 2025
- Assembly type
- DC
- Serial number
- A261728
- Size
- 1
- Test gauge serial
- G-1474
- Gauge calibration date
- Aug 6, 2024
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Brandt, current on the service date
- All required fields present
- Address matches parcel 055-85-01298
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.