Back to the backflow review queue

Backflow assembly test: 1913 Ridgeview Ln

Approved

Filed Dec 12, 2024 by Hayden Fairley, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 12, 2024
Assembly type
RP
Serial number
K780334
Size
1
Test gauge serial
G-7734
Gauge calibration date
Apr 10, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Fairley, current on the service date
  • All required fields present
  • Address matches parcel 055-71-01303
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1913 Ridgeview Ln
Owner: Taylor Brandt
Parcel 055-71-01303