Back to the backflow review queue

Backflow assembly test: 1913 Ridgeview Ln

Approved

Filed Dec 18, 2025 by Cameron Ellery, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 18, 2025
Assembly type
RP
Serial number
K780334
Size
1
Test gauge serial
G-8658
Gauge calibration date
Apr 28, 2025
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Ellery, current on the service date
  • All required fields present
  • Address matches parcel 055-71-01303
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1913 Ridgeview Ln
Owner: Taylor Brandt
Parcel 055-71-01303