Back to the backflow review queue

Backflow assembly test: 1522 Laurel Rd

Approved

Filed Jul 4, 2026 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 4, 2026
Assembly type
PVB
Serial number
B300862
Size
1
Test gauge serial
G-6925
Gauge calibration date
Mar 1, 2026
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-17-01294
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1522 Laurel Rd
Owner: Avery Brandt
Parcel 055-17-01294