Backflow assembly test: 1600 Hickory Trl
ApprovedFiled Jul 22, 2025 by Alex Okafor, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 22, 2025
- Assembly type
- DC
- Serial number
- A537196
- Size
- 1
- Test gauge serial
- G-8462
- Gauge calibration date
- Dec 7, 2024
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Okafor, current on the service date
- All required fields present
- Address matches parcel 055-45-01107
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.