Backflow assembly test: 4324 Ridgeview Dr

Approved

Filed Sep 18, 2026 by Emerson Calloway, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 18, 2026
Assembly type
PVB
Serial number
Z198757
Size
1
Test gauge serial
G-3696
Gauge calibration date
Jul 5, 2025
Check valve 1
0.9 psid
Check valve 1 closed tight
No
Check valve 2
2.4 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Calloway, current on the service date
  • All required fields present
  • Address matches parcel 055-21-01354
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4324 Ridgeview Dr
Owner: Hayden Kessler
Parcel 055-21-01354