Back to the backflow review queue

Backflow assembly test: Main Street Self Storage

Approved

Filed Jun 16, 2024 by Hayden Fairley, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 16, 2024
Assembly type
RP
Serial number
Z361334
Size
2
Test gauge serial
G-9718
Gauge calibration date
Apr 9, 2024
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Fairley, current on the service date
  • All required fields present
  • Address matches parcel 055-79-01267
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3107 Laurel Ln
Owner: Wexler Holdings LLC
Parcel 055-79-01267