Back to the backflow review queue
Backflow assembly test: Maple Leaf Animal Hospital
Needs reviewFiled Nov 20, 2026 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 20, 2026
- Assembly type
- RP
- Serial number
- B165067
- Size
- 4
- Test gauge serial
- G-2206
- Gauge calibration date
- Sep 8, 2026
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Brandt, current on the service date
- All required fields present
- Address matches parcel 055-67-01315
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
1087 Sycamore Way
Owner: Nguyen Holdings LLC
Parcel 055-67-01315