Back to the backflow review queue

Backflow assembly test: Blue Heron Taqueria

Approved

Filed Jan 26, 2024 by Parker Brandt, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 26, 2024
Assembly type
RP
Serial number
B579787
Size
1
Test gauge serial
G-4536
Gauge calibration date
Sep 15, 2023
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
4.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Brandt, current on the service date
  • All required fields present
  • Address matches parcel 055-38-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4098 Cedar Hollow Trl
Owner: Whitcomb Holdings LLC
Parcel 055-38-01327